AIR/OIL RATIOTROL
AIR/OIL RATIOTROL
Axis air/oil ratiotrol -7052 proportion oil flow to combustion air flow in cross-connected control systems. Outlet oil pressure from the ratiotrol is proportional to the impulse air signal:
7052-01: Outlet pressure is 10 times impulse pressure.
7052-0: Outlet pressure is 12 times impulse pressure
Therefore, as combustion air is turned up or down the ratiotrol causes oil to follow it in proportion. Desired air/oil ratio is set with a manual – valve (1813 Sensitrol Oil Valve) at the burner.
MULTIPLE BURNERS
A single Ratiotrol can serve burners when it is cross-connected down stream of the zone air control valve if burners are on one side of furnace an difference in their elevation is less than 12”.
Air Impulse Pressure, PSI |
||||
---|---|---|---|---|
Ratiotrol |
0.5 |
0.75 |
1 |
1.5 |
7052-01 | 194.7 | 237.18 | 276.12 | 336.3 |
7052-01-V | 127.44 | 159.3 | 184.08 | 223.02 |
7052-0 | 569.94 | 697.38 | 803.58 | 969.96 |
7052-0-V | 357.54 | 435.42 | 502.68 | 605.34. |
EXPANSION CHAMBERS
If ratiotrol is in light oil line between valves that are closed when burners are shut off, radiant heat from furnace could expand oil trapped in the line, brusting ratiotrol diaphragms and damaging gauges. Install one of more 8521-01 expansion chambers down stream of ratiotrol to prevent this.
SPECIFICATIONS
Inlet oil pressure | 25-30 PSI (Important for proper operation) |
Maximum oil temperature | 180 F for standard 7052 300 F for 7052-0-V(with viton diaphragms) |
Oil gauges : 7052-01 | Light oil only |
7052-0 | #1through#6 probably requires special construction and other provisions, e.g., V Viton diagraphms |
Optional Gauges (and thermometer) 7052-01 |
Inlet and outlet pressure, air impulsepressuredial thermometer |